| Standard | IEC 61439 1 2011 Part 1: General rules IEC 61439 6 2012 Part 6: Busbar trunking systems (busway) |
|---|
| Compliance | IEC/EN 61439-6, BS EN 60529, IEEE, IS 8364, NEMA and UL |
|---|
| Test Certifications | HV&SC – NTDC Rawat (KEMA Accredited Lab) PCSIR Lab |
|---|
| Busbar Construction | Insulated Sandwich Busway |
|---|
| Standard Length | 3 meters |
|---|
| Tap-off point | Up to 3 per 3 m length (per side) |
|---|
| Tap-off Unit | Up to 1250 A |
|---|
| Busbar Insulation | Epoxy & Mylar (Class B) |
|---|
| Rated Frequency | 50/60Hz |
|---|
| Current Rating | 250A – 6300A (Al) 250A – 6300A (Cu) |
|---|
| Rated peak withstand current (Ipk) | 63 – 330 kA for 1 sec |
|---|
| Rated short-time withstand current (Icw) | 30 – 150 kA for 1 sec |
|---|
| Rated operational voltage (Ue) | 1000 V |
|---|
| Rated insulation voltage (Ui) | 1000 V |
|---|
| Rated impulse withstand voltage (Uimp) | 12 kV |
|---|